To check power on an industrial tour, find the main switchgear and read the nameplate for voltage, phase, and amps, then ask for the transformer size, 12 months of electric bills, and the one-line diagram. To check loading docks, count dock-high and drive-in doors, measure them, test the levelers, seals, and restraints, and walk the truck court to confirm a 53-foot trailer can back in. The listing flyer is a starting point, not the answer. What matters is how much power is actually available for your equipment and whether the docks work for the trucks you run.
Checking electrical power
Find the main service and read the nameplate
Ask to see the electrical room before you look at anything else. The main switchgear or panel has a nameplate that lists three numbers you need:
- Voltage. Industrial users usually want 277/480 volts. Many older and multi-tenant buildings in the suburbs run on 120/208 volts, which is fine for warehousing but limits heavy machinery.
- Phase. Three-phase power is standard for industrial equipment. Single-phase is a red flag for manufacturing.
- Amps. The rating of the main breaker, such as 400, 800, or 1,200 amps.
Convert it to something comparable
Amps alone can mislead, because 400 amps at 208 volts is far less power than 400 amps at 480 volts. The quick conversion is volts times amps times 1.732, divided by 1,000, which gives capacity in kVA.
| Service | Approximate capacity |
|---|---|
| 208V, 3-phase, 400A | 144 kVA |
| 480V, 3-phase, 400A | 333 kVA |
| 480V, 3-phase, 800A | 665 kVA |
| 480V, 3-phase, 1,200A | 998 kVA |
Those are the size of the pipe, not what is left in it. Usable capacity depends on the transformer, the utility feed, and whatever is already drawing power.
Ask what is actually available
The most important power question on any tour is: what is the building’s peak measured demand, and how much load can I add without upgrading the service? To answer it, ask for:
- The last 12 months of electric bills, which show peak demand.
- The electrical one-line diagram.
- The transformer kVA rating, and whether the transformer belongs to the utility or the building.
- Whether the space is separately metered or shares service with other tenants.
- Any recent electrical inspection or engineering report.
Know who supplies the power
In Lake County, Illinois and most of northern Illinois, the utility is ComEd. In Kenosha and Racine, it is We Energies. If you need more power than the building has, the utility has to confirm capacity at the street, and a service upgrade can take months and cost far more than tenants expect. Ask early, and if you are leasing, decide in the letter of intent who pays for an upgrade. That is a negotiating point, not an afterthought.
Checking loading docks
Count and measure
Record the number of dock-high doors and drive-in doors, then measure them. Common dimensions in suburban Chicago industrial buildings:
| Feature | Common dimensions |
|---|---|
| Dock door | 8 to 9 feet wide, 9 to 10 feet high |
| Dock height | 48 to 52 inches above grade |
| Drive-in door | 10 to 14 feet wide, 12 to 16 feet high |
These are typical, not standards. Older buildings often have shorter dock heights or narrower doors, which matters if you run specialized trailers.
Test the equipment
- Levelers. Pit levelers handle more trailer height variation than edge-of-dock plates. Run them.
- Seals and bumpers. Torn seals mean heat loss in a Chicago winter. Missing bumpers mean building damage.
- Trailer restraints and dock lights. Check that they work.
- Overhead doors. Open and close every one you plan to use.
Then ask who owns and maintains the dock equipment. It is often the tenant’s responsibility under an industrial net lease.
Walk the truck court
This is the step most people skip. Go outside and picture a tractor-trailer backing into each door:
- Is the truck court deep enough for a 53-foot trailer to back in without blocking the drive aisle? Around 120 to 130 feet is typical for modern distribution buildings, and older suburban buildings often have less.
- Can more than one truck load at the same time?
- Is there room for trailer parking or a staging lane?
- Are there shared drives, easements, or village restrictions on truck routes or overnight parking?
Match the docks to your operation
A distribution user may need one dock door for every 5,000 to 10,000 square feet. A light manufacturer may need two docks and one drive-in. Count your daily inbound and outbound trucks, and size the requirement from that, not from what the building happens to have.
A quick tour checklist
- Voltage, phase, and amps from the nameplate
- Transformer kVA and ownership
- 12 months of bills and peak demand
- Separate meter or shared service
- Dock and drive-in door count and dimensions
- Levelers, seals, bumpers, and restraints tested
- Truck court depth and 53-foot trailer access
- Maintenance responsibility for docks and electrical
- Who pays for any power or dock upgrades
For more on dock layout, see our guide to assessing loading docks and drive-in doors. For current industrial availability and rents, check the daily-updated RFP Chicagoland Commercial Real Estate Index, or have the Van Vlissingen and Co. industrial team pre-screen buildings for your power and loading requirements before you tour.
Frequently asked questions
How do I know how much power an industrial building has?
Read the main switchgear nameplate for voltage, phase, and amps, then ask for the transformer kVA rating, the one-line diagram, and 12 months of electric bills to see peak demand and remaining capacity.
What voltage do industrial buildings use?
Most industrial users want 277/480 volt, three-phase service. Many older and multi-tenant buildings have 120/208 volt service, which supports warehousing but can limit heavy equipment.
How long does it take to upgrade power to an industrial building?
It depends on the utility and the size of the upgrade, but a service upgrade can take months. Confirm capacity with the utility early and settle who pays for the upgrade in the letter of intent.
What is a standard loading dock height?
Most dock-high doors sit 48 to 52 inches above grade, with doors around 8 to 9 feet wide and 9 to 10 feet high.
How deep should a truck court be?
Around 120 to 130 feet is typical for modern distribution buildings handling 53-foot trailers. Older suburban buildings often have shallower courts, so walk it before you commit.